Inspecting electrical enclosure interiors is required by most standards of practice but presents safety risks. This episode teaches you how to inspect safely and effectively while identifying critical defects that could cause fires or electrocution.

Safety Risks and Precautions:

  • Electrocution risk: touching energized parts
  • Arc-flash risk: sparks between energized and grounded parts
  • Safety techniques: back of hand test, rubber-soled shoes, safety glasses
  • When NOT to inspect enclosure interiors
  • What to report when inspection isn't performed

Overcurrent Protection Devices (OPDs):

  • Purpose: Prevent overcurrent and short circuits from causing fires
  • Fuses: Edison base (Type T), Type S, cartridge types
  • Overfusing dangers (penny in fuse holder)
  • Circuit Breakers: Thermal-magnetic trip technology
  • Full-height, half-height, and tandem configurations
  • Service life: 30-50 years
  • Compatible breakers (must match panelboard manufacturer)

GFCI Protection:

  • Detects ground faults (~6 milliamperes difference)
  • Required locations: kitchens, bathrooms, garages, laundry, basements, outdoors, crawl spaces
  • Testing methods (TEST button recommended)
  • Can work without equipment ground (EGC)

AFCI Protection:

  • Detects arcing faults (parallel and series)
  • Required for most 15/20-amp, 120V branch circuits
  • Branch/feeder type vs. combination type
  • Testing considerations in occupied vs. unoccupied buildings

Conductor and OPD Compatibility:

 | Wire Size | Max OPD Rating
| #14 AWG | 15 amps
| #12 AWG | 20 amps
| #10 AWG | 30 amps
| #8 AWG | 40 amps

Panelboard Types:

  • Single-bus panelboards (most common)
  • Split-bus panelboards (no main breaker, "rule of six")
  • Main breaker vs. main lug panels
  • Meter-main enclosures

Location, Access, and Working Clearances:

  • 36" deep x 30" wide x 78" tall working space
  • Equipment not allowed: storage spaces, closets, bathrooms, above stairs
  • Maximum height: 79" to circuit breaker handle
  • Must be readily accessible (no climbing over objects)

Multiple Conductors in One Lug:

  • General rule: ONE conductor per lug (except as labeled)
  • EGCs: TWO same-size conductors per lug allowed
  • Exception: Some Square D/Homeline breakers have double saddles
  • Danger: Multiple conductors may not be properly protected

Typical Defects to Report

  • Rust (indicates water leaks)
  • Paint/drywall compound in enclosure
  • Missing handle ties on 240V circuits
  • Absent tabs/knockouts (shock hazard)
  • Pointed screws on covers (could energize enclosure)
  • Excess uninsulated conductor at breakers
  • Low-voltage components inside high-voltage enclosures
  • Fused neutrals (very old systems)
  • Conductors not straight in lugs
  • Branch circuits not labeled
  • Too many circuit breakers for panelboard rating
  • Panelboard ampacity exceeds feeder conductor capacity
  • Cables not secured to enclosure

Key Takeaways

  • Never assume circuits are de-energized
  • You're not required to inspect if you believe it's unsafe
  • Circuit breakers have finite service life (30-50 years)
  • GFCI protects people; AFCI protects structures
  • Multiple conductors in one lug can be extreme